A chiller in Ohio gets a winter off. A chiller in Fort Lauderdale does not. Ours run ten, eleven, sometimes twelve months a year, in high humidity, with cooling towers pulling in salt and dust from the air. That is why maintenance schedules written for northern climates do not fit here. You need to do more of it, and you need to do it on a calendar that does not assume a long shutdown season.

This is the checklist we use for water cooled chillers in commercial buildings across Broward, Miami Dade and Palm Beach. It is not a substitute for the manufacturer's manual, and it lines up with the approach in ASHRAE Standard 180, which covers inspection and maintenance of commercial HVAC systems. Think of it as the version a building engineer can actually work from.

The single best maintenance habit is a daily log. Write down, or have the building automation system record:

Evaporator and condenser refrigerant pressures or saturation temperatures

The numbers by themselves do not mean much. The trend is what matters. If the condenser approach creeps up a degree or two over a few months, the tubes are fouling. If the evaporator approach rises, you may be low on refrigerant or have a fouled evaporator. A log turns a surprise breakdown into a planned repair.

Walk the plant. Look and listen. Check for oil leaks, refrigerant leak signs, unusual vibration and noise. Look at the sight glasses. Verify the flow switches work, because a chiller that loses water flow without tripping can freeze an evaporator tube and that is an expensive day.

Check the cooling tower too. In South Florida, the tower is where most of the trouble starts. Look at the basin, the fill and the drift eliminators. Confirm the water treatment system is feeding chemicals and the conductivity controller is bleeding off. Clean strainers.

Inspect pumps and motors. Bearings, couplings, seals and amps. A pump that is drawing more current than last month is telling you something.

Pull an oil sample and send it for analysis. Oil analysis shows wear metals, moisture and acid before they cause a failure. It is cheap compared to a compressor.

Check refrigerant charge and run a leak check. Larger systems are subject to EPA leak repair rules under Section 608 of the Clean Air Act, and newer rules under the AIM Act extend leak management to many HFC systems. Your technician should know which rules apply to your equipment and keep the required records. Either way, a leaking chiller costs money every day it runs.

Verify controls and safeties: low pressure cutout, high pressure cutout, freeze protection, motor overloads. Calibrate temperature sensors. A sensor that reads two degrees off can waste a lot of energy or cause nuisance trips.

Clean the condenser tubes. In South Florida, many buildings should do this at least once a year, and some plants with hard water or tower problems need it more often. Fouled tubes drive up head pressure and energy use. While the heads are off, inspect the tube sheets and gaskets.

Eddy current test the tubes on a regular cycle, often every few years depending on the age of the machine and what earlier tests showed. Eddy current testing finds thinning and pitting before a tube leaks. A tube leak in a water cooled chiller can put water into the refrigerant circuit, which turns a routine repair into a major one.

Inspect the evaporator. Closed chilled water loops stay cleaner than condenser loops, but they still need water treatment and periodic inspection.

Check the motor. Megger test the windings, inspect the starter or variable frequency drive, tighten electrical connections and look for heat damage. An infrared scan of the electrical gear feeding the chiller is a good idea while you are at it.

Do a full controls review. Check setpoints, reset schedules, staging and the interface with the building automation system. A lot of plants are running the same setpoints someone typed in years ago.